EA803 series 10 ~ 200 kVA
Descrição do Produto
EA803 EA803 series 10 ~ 200 kVA The EA803 offers high performance and three phase uninterruptible power for data centre and critical environments which demand maximum uptime without interruption.
Table of contents 5
Introduction
8
Reliability
10
LCD Display
11
Batteries
EA803 series
12
Battery Monitoring
13
Services
10 ~ 200 kVA
14
Control
16
Weight and dimensions
18
Technical data sheet EA803
Introduction The EA803 provides a solid foundation for today’s high availability equipment, giving users critical and clean power, 24/7, without interruptions. The cost effective EA803 UPS systems are equipped with advanced features such as true online double conversion technology, a user friendly touch screen display, generator compatibility, and optional control through the network. With its wholly reliable performance, EA803 solutions are widely deployable, making them the answer to all of your high performance demands.
True Online Double Conversion The EA803 applies true online double conversion technology, providing users with clean and high quality power. The zero transfer time ensures that power is supplied without interruption, thereby fully protecting mission-critical devices.
Where will you be when the lights go out?
Wide Input Voltage Range The EA803 provides stable power to connected devices in unstable power conditions. It is capable of handling a wide input voltage range, supplying clean power in extreme circumstances.
Pure Sine-wave The pure sine-wave output of the EA803 guarantees compatibility with various applications, including those that are high performance, industrial, or mission critical.
Front view of the EA803 15kVA
The true online double conversion technology overview
4
EA803 SERIES / www.eastups.eu
EA803 SERIES / www.eastups.eu
5
Self-diagnosis at UPS Start Up Fans on the back of the EA803 10kVA
The UPS will perform advanced self-diagnostics to ensure the functionality of the UPS system and batteries, and to anticipate events before they occur.
IGBT The Insulated Gate Bipolar Transistor (IGBT) is a power semiconductor device for high efficiency and fast switching, providing more reliable, clean and high efficiency power to the UPS, which is critical when using electrical equipment.
Cold Start
The front view of the EA803 60 and 160kVA UPS
In the absence of any AC input, the cold start function allows users to start the UPS with the batteries, and without any damage to them or the circuits. This means that users can easily configure the UPS, even if no AC input is connected.
Lightning and Surge Protection Optional Emergency Power Off (EPO) Function The EA803 is equipped with an Emergency Power Off function, providing users with a way of immediately shutting down all output power from the UPS in the case of emergencies such as fire, flood, and overheating equipment.
6
EA803 SERIES / www.eastups.eu
The EA803 UPS systems come with lightning and surge protection as standard, thus protecting the equipment against voltage spikes. Surge protection works by channeling the extra voltage into the outlet’s groundning wire, preventing it from flowing through electronic devices, while also allowing normal voltage to be maintained.
Variable Fan Speed The intelligent variable fan speed ensures that the speed of the fans is adjusted to the amount of load and heat dissipation of the UPS.
Short Circuit and Overload Protection A short circuit is an abnormal connection between two nodes of an electrical circuit, and can cause huge damage to the UPS and any equipment attached to it. The EA803 circuit protection device will protect against potential short circuit damage, overheating, fire, or even explosions. The UPS is also equipped with overload protection, meaning that the fuse will automatically be triggered when a load exceeds its value. Both protection devices ensure the safety and reliability of the UPS and any equipment that is attached to it.
EMI RFI Noise Filter Electromagnetic interference (EMI or radio frequency interface, RFI) is a disturbance which affects an electrical circuit. The EMI RFI Noise Filter will protect the UPS system against any interference which may interrupt the effective performance of the device.
EA803 SERIES / www.eastups.eu
7
Reliability In today’s business environment, it is important to have a power infrastructure available 24/7. The EA803 is extremely reliable through the redundant design of the internal components.
Manual Bypass Switch Maintenance work can be carried out through the use of the manual bypass switch. This completely isolates the UPS’s internal components, so that minor maintenance work and repairs can be conducted without interruption to supply.
Optional External Bypass Switch The external bypass switch ensures that there is continuous power to the equipment by completely isolating the UPS bridging between it and the mains. Using this tool, users have the ability to carry out substantial interventions and even change a UPS without interruption to supply.
Front side of the EA803 10kVA
AC
Generator
Input
Bypass Automatic Bypass Switch
Component trays can be easily accessed for maintenance
The EA803 is also equipped with automatic and manual transfer switches as standard, guaranteeing that power will be supplied to the load and, therefore, the equipment, even during maintenance.
8
EA803 SERIES / www.eastups.eu
The automatic bypass will switch the input from the mains directly to the output of the UPS in the event of overloading or failure of the system. This guarantees continuous power to the output without interruption.
UPS 1
BAT 1
UPS 1
BAT 1
BYPASS
Output Load
EA803 SERIES / www.eastups.eu
9
LCD Display
Batteries
The LCD display combines functionality with the provision of instant access to details of all of a system’s conditions and statuses, meaning that valuable critical data is always at an operator’s finger tips.
The need to have reliable batteries is extremely important. EAST has years of experience in the design and manufacturing of high quality batteries and through the use of the latest charging and discharging technologies you are assured that they keep supplying that critical power.
Advanced Battery Management
Extended Runtime
The EA803 UPS systems are equipped with a sophisticated three step charger for efficiently charging the UPS while prolonging battery life.
By adding one or more battery cabinets to the configuration, it is easy to increase the runtime of the system from several minutes up to several hours, creating a custom solution which will meet users’ varied business demands.
Charge Voltage (V)
Charge Current (A)
90%
100%
Capacity
Step 1 The charger provides a constant charge current until the battery has reached 80% of its capacity, meaning that the UPS is ready to operate again when a new power failure occurs. The LCD display displaying all relevant information
Touch screen LCD display The UPS is equipped with an LCD touch screen display, meaning that it is easy to manage. Information such as operational status and procedures, measurements, values, and failure records will all be displayed.
10
EA803 SERIES / www.eastups.eu
Users can view major system values and conditions:
UPS information Input Output Load information Battery History Settings System diagnostics
Step 2 The charge voltage is held constant for about 60 minutes, allowing the charge current to gradually decline towards the end of this period. The battery will now have been charged to about 90% of its capacity. Step 3 The charge voltage drops to a float-charge in order to compensate for self discharge, thereby prolonging the life of the batteries.
Sealed Lead Acid batteries providing power to the EA803 in case of a power failure
Batteries The batteries are Valve-Regulated Maintenance Free Sealed Lead-Acid, and utilize state of the art Oxygen Recombination technology. EAST has several years of experience in the design and manufacturing of high quality NP series batteries. Their fully sealed structure, long life, reliability and quality make them more convenient to use and the solution to the significant demands of today’s business environment.
The EA803 is equipped with an automatic and manual transfer switch as standard, guaranteeing that power is supplied to the load, even during maintenance procedures.
EA803 SERIES / www.eastups.eu
11
Battery Monitoring Features: Completely maintenance-free Leakage proof Safe, flame-protected Low inner resistance; an excellent discharge in the case of a large current Long life; 3-5 years for the NP series Wide operating temperature (-35 to 45°C) No dissociated electrolyte; position independent Low self-discharge Unique engineering design; good recovery capability from deep discharge Optional 12 year gel batteries are available
BAT monitoring device (BMD)
BMD
BM
BAT
BM
BAT
BM
BAT module (BM)
BAT
Batteries
Instalation Services Start Up Service
Going Live Service
By letting an EAST certified engineer conduct your installation, you are certain to save both time and money. With our professional approach and knowledge, we will install all of your EAST products, thereby ensuring their safety and lifespan. The start up service includes the on site installation and commisioning of your UPS systems and batteries, with the guarantee that the products will function according to EAST standards.
This is an extra feature which includes having an EAST certified engineer present on site at the time when your configuration goes live. This means that there is both an extra helping hand available if something need to be explaned and an extra quality check of the installation.
As a unique feature, EAST has included the installation of its licence free software in the start up service. EAST will perform on site installation and intergration of all EAST software.
Schematic overview of the battery monitoring system
Extra Service Support
The system monitors the charge and discharge current, temperature, and quality of each individual battery, ensuring a constant and reliable power supply to the UPS. Each individual battery is monitored through the BAT module, which is connected to the positive and negative poles of the battery. This module tests and monitors the battery and relays all relevant information to the BAT monitoring device.
The 60 kVA EA803 with fully digital control
12
EA803 SERIES / www.eastups.eu
Preventive Maintenance Once your confirguration is operational and active, you want to be confident that its performance is as efficient as possible. To ensure the life of the batteries and UPS system, we offer a preventive maintenance service whereby an EAST certified engineer will come on site to check all of your EAST products. During this process, the engineer will run several tests and carry out any maintenance work when required to do so.
The unique EAST BAT system provides the operator with in-depth knowledge and control of the batteries connected to the EA803. The BAT system guarantees optimal capacity and runtime throughout the life of the battery, ensuring that there is no loss of investment due to faulty batteries.
The operator can monitor and set predetermined thresholds in the system through the user-friendly web interface or the LCD display positioned on the side of the battery cabinets.The system can also be fully integrated with a building management system through the use of the industry standard SNMP protocol for communication.
Maintenance Services
The standard service support may not always meet your needs, and in these circumstances you can extend the help available to you by taking out one of our extra service support packages. These come in two different sizes: 1) 9x5: five days a week, nine hours a day 2) 24x7: seven days a week, 24 hours a day
The service engineers of EAST UPS are available 24/7 to assist you.
During the hours that support is available to you, the services on offer include full assistance via a customer help-line and email, next day on site repair or replacement, and a response time of four hours.
EA803 SERIES / www.eastups.eu
13
Control RS232 + Dry contact
M onitoring and management of the EA803 using a standard web browser or SNMPview capable of monitoring up to 1000 pieces in one view Remote control and rebooting of UPSprotected devices over the network Using the licence free software, protection of user information through the automatic shutdown of multiple UPS-protected devices during an extended power failure Real-time email alarm notification Real-time SMS alarm notification with SMS server software (additional hardware required) Supports standard UPS MIB for third-party network management software Multi language web interface PDA/WAP interface for management through the internet or network when users are on the move Client software is licence free, with no additional fees, and is available for Windows, Linux
The EA803 is equipped with a multifunctional RS232 port. This can be used for dry contact, supplying relay functionality for a low battery, AC fail, and other common failures of customwired applications. It can also be connected to a computer or server for the standard shutdown software.
Standard Shutdown Software The EA803 is able to automatically shut down the server or computer when a power failure occurs. This software enables the UPS to instruct the operating systems to close down a PC when it is running unattended. Users can set the parameters with which to schedule the computer or server to shutdown, making sure that no significant data is lost and important backups are created. Updates will be automatically sent by email, so that users are always aware of what is happening, even at remote locations.
Communication Slot The multifunctional communication slot is conveniently located at the back of the UPS and can be used to accommodate a variety of accessory cards. The wide range of cards that are available means that the EA803 can be used for various applications and in numerous locations.
Intergration with the Building Management System
SNMP Card The SNMP card allows users to connect the EA803 directly to the ethernet network and the internet. This solution means that users can conveniently monitor and manage the UPS with a standard web browser, while simultaneously being able to shutdown multiple computers and operating systems over the network.
The EA-SNMP internal communication card
14
EA803 SERIES / www.eastups.eu
HTTP, SNMP, SMTP, WAP, Telnet, SSL, SSH, SNMPV3, Radius, and MODBUS on TCP/IP compatibility; dynamic and versatile support for a wide variety of system configurations
Back of the EA803 10kVA
Environmental Card
GPRS Card
The environmental card provides the functionality with which to remotely monitor environmental and UPS conditions using a standard web browser, SNMPview, or third-party network management software. Users can observe the ambient temperature, humidity, or the presence of water in the remote location, along with the status of additional contact devices such as a smoke detector or an open-door/window sensor.
The GPRS card can be used with the EA803 and enables the user to have an in depth overview of the status of the UPS and the power at a particular location without any network or internet connection. The status can be viewed using the web interface, SNMPview or third-party network management software. As long as there is GPRS coverage, users will be able to deploy this card.
Relay I/O Card
USP’s
The Relay I/O card can be inserted in the SNMP slot at the back of the UPS, providing dry contact relay outputs for custom-wired applications and delivering support for the built-in shutdown of AS/400 systems. This option provides contact closures for the remote monitoring of alarm conditions in the UPS, delivering signals for On Battery, On Bypass, Low Battery, Summary Alarm, UPS Fault and On UPS.
Software license free Monitor 1000 UPS systems in a single view Diversity of Operating Systems supported Integrate with your Building Management System or Network Management System Real-time email and SMS alarm notification Monitor suroundings in real-time via environmental sensors
EA803 SERIES / www.eastups.eu
15
Weight and dimensions Front
Back
Front
1680 mm
1140 mm
Back
1140 mm
Front
450 mm
450 mm
EA803
EA803
EA803
EA803
EA803
10kVA
15kVA
20kVA
30kVA
40kVA
Weight Height Depth Width
208 kg 1140 mm 730 mm 450 mm
220 kg 1140 mm 730 mm 450 mm
240 kg 1140 mm 730 mm 450 mm
316 kg 1140 mm 855 mm 450 mm
334 kg 1140 mm 855 mm 450 mm
Front
The 120 kVA EA803
Back
Back
EA803
EA803
EA803
60kVA
80kVA
100kVA
Weight Height Depth Width
650 kg 1500 mm 855 mm 710 mm
Weight Height Depth Width
900 kg 1680 mm 860 mm 1100 mm
950 kg 1680 mm 860 mm 1100 mm
EA803
120kVA
Weight Height Depth Width
1050 kg 1680 mm 860 mm 1100 mm
1500 mm
1680 mm
710 mm
16
EA803 SERIES / www.eastups.eu
1100 mm
EA803 SERIES / www.eastups.eu
17
Technical data sheet EA803 (10-60 kVA)
Technical data sheet EA803 (80-200 kVA)
EAST UPS Europe B.V. technical data sheet EA803 [True Online Double Conversion 10 - 60 kVA, 3 phase in/ 3phase out] Model kVA Rating Real Power Rating
EA803-10
EA803-15
EA803-20
EA803-30
EA803-40
EA803-60
10 kVA
15 kVA
20 kVA
30 kVA
40 kVA
60 kVA
8000 Watt
12000 Watt
16000 Watt
24000 Watt
32000 Watt
48000 Watt
Input
EAST UPS Europe B.V. technical data sheet EA803 [True Online Double Conversion 80 - 200 kVA, 3 phase in/ 3phase out] Model kVA Rating Real Power Rating
EA803-80
EA803-100
EA803-120
EA803-200
80 kVA
100 kVA
120 kVA
160 kVA
200 kVA
64000 Watt
80000 Watt
96000 Watt
128000 Watt
160000 Watt
Input
Phase
3 Phases + N + G
Phase
3 Phases + N + G
Voltage
380V ± 25%
Voltage
380V ± 25%
Frequency
50/60Hz ± 5%
Power Factor
Frequency
0.92
Soft Start
50/60Hz ± 5%
Power Factor
0 ~ 100% 5s
0.92
Soft Start
Bypass Input
0 ~ 100% 5s
Bypass Input
Phase
3 Phases + N + G
Phase
380V ± 25%
Voltage
Voltage Frequency
50/60Hz ± 5%
Transfer Time
3 Phases + N + G 380V ± 25%
Frequency
0ms, Inverter/Bypass (Overload)
50/60Hz ± 5%
Transfer Time
DC System
0ms, Inverter/Bypass (Overload)
DC System 360V (Rated Voltage)
Voltage
360V (Rated Voltage) Voltage
405V (Float Charge Voltage)
405V (Float Charge Voltage)
315V (Shutdown Voltage) Current
EA803-160
28 A
42 A
Charge Current
56 A
315V (Shutdown Voltage)
85 A
113 A
169 A
1 ~ 30A (Adjustable depending on batteries)
Current
225 A
Charge Current
AC Output
282 A
338 A
381 A
507 A
1 ~ 30A (Adjustable depending on batteries)
AC Output
Phase
3 Phases + N + G
Phase
3 Phases + N + G
Voltage
380V ± 1% (Stable Load); 380V ± 5% (Fluctuated Load)
Voltage
380V ± 1% (Stable Load); 380V ± 5% (Fluctuated Load)
Frequency
50 ~ 60Hz ± 0.5Hz (Battery Mode)
Power Factor
Frequency
0.8
50 ~ 60Hz ± 0.5Hz (Battery Mode)
Power Factor
0.8
Wave
True Sine Wave
Wave
True Sine Wave
THDi
Total Harmonic Distortion ≤ 3% (Linear Load); ≤ 5% (Non-Linear Load)
THDi
Total Harmonic Distortion ≤ 3% (Linear Load); ≤ 5% (Non-Linear Load)
Transient Recovery Time ≤ 10ms
Time
Time Overload
125% for 10 minutes; 150% for 1 minute
Cooling
Forced Wind
125% for 10 minutes; 150% for 1 minute
Cooling
Panel Display LCD/LED
Transient Recovery Time ≤ 10ms
Overload
Forced Wind
Panel Display User Friendly interface via touch screen LCD display; Load/Battery capacity; Online; battery status; overload etc.
General
LCD/LED
User Friendly interface via touch screen LCD display; Load/Battery capacity; Online; battery status; overload etc.
General
Efficiency
91%
Communication
Efficiency
RS232; Optional SNMP
Noise
48 ~ 60db
Communication 53 ~ 65db
Temperature
RS232; Optional SNMP
Noise
0 ~ 40ºC (Operating)
Humidity
95% 55 ~ 65db
Temperature
30 ~ 90% (non-condensing)
0 ~ 40ºC (Operating)
Humidity
30 ~ 90% (non-condensing)
Isolation Transformer Optional
Isolation Transformer Optional
Harmonic Suppression Filter
Harmonic Suppression Filter
Parallel Function Dimension (mm) Net Weight (Kg)
450 x 730 x 1140 208
Packing Dimension Gross Weight (Kg)
220
232
248
240
EA803 SERIES / www.eastups.eu
316
334
520 x 930 x 1400 265
Product Specifications are subject to change without further notice, © East Ups Europe
18
Parallel Function 450 x 855 x 1140
520 x 800 x 1300
60 ~ 65db
346
364
710 x 855 x 1500
Dimension (mm)
650
Net Weight (Kg)
780 x 940 x 1660
Packing Dimension
695
Gross Weight (Kg)
1100 x 860 x 1680 900
950
1800 x 1100 x 1680 1050
1180 x 940 x 1850 965
1015
2100
3200
1880 x 1180 x 1850 1115
2195
3295
Product Specifications are subject to change without further notice, © East Ups Europe
EA803 SERIES / www.eastups.eu
19
East UPS Europe b.v.
EAST ups middle east trading fze
Weiland 1C NL-6666 MH, Heteren The Netherlands
P.O. Box 10559 Ras Al Khaimah United Arab Emirates
T +31 26 47 90 790 F +31 26 47 43 704
T +971 (0) 7 2 076 609 F +971 (0) 7 2 041 010
www.eastups.eu
www.eastups.ae
Lihat lebih banyak...
Comentários